Introduction
Accurate HVAC load calculation is the first step in designing any air conditioning or heating system. It determines the amount of cooling or heating required to maintain a comfortable indoor environment.
Tip for Beginners: Always consider both sensible heat (temperature change) and latent heat (humidity/moisture load) in calculations.
Key Formulas
-
Sensible Heat Load:
-
Q_s: Sensible heat (Btu/hr)
-
CFM: Airflow (cubic feet per minute)
-
ΔT: Temperature difference (°F)
-
Latent Heat Load:
-
ΔW: Difference in humidity ratio
-
Total Heat Load:
-
Δh: Change in enthalpy
Sensible Heat Load:
Q_s: Sensible heat (Btu/hr)
CFM: Airflow (cubic feet per minute)
ΔT: Temperature difference (°F)
Latent Heat Load:
ΔW: Difference in humidity ratio
Total Heat Load:
Δh: Change in enthalpy
Example Calculation
-
Room: 20 × 15 ft, 9 ft ceiling
-
Airflow: 800 CFM
-
Temperature difference: 75°F indoor – 95°F outdoor = 20°F
-
Sensible Heat:
Room: 20 × 15 ft, 9 ft ceiling
Airflow: 800 CFM
Temperature difference: 75°F indoor – 95°F outdoor = 20°F
Sensible Heat:
(You can expand with latent heat example and total heat load calculation.)
Practical Tips
-
Use psychrometric charts for accuracy.
-
Always include safety margins (10–15%) for peak load.
-
Document all assumptions for future reference.
Use psychrometric charts for accuracy.
Always include safety margins (10–15%) for peak load.
Document all assumptions for future reference.
Suggested Images
-
Psychrometric chart example.
-
Step-by-step calculation table.
Psychrometric chart example.
Step-by-step calculation table.
Internal Linking:
-
Link to Duct Design page for airflow considerations: Duct Design and Airflow Formulas
Link back to Master Page: HVAC Formulas Master Guide
Tags:
HVAC load calculation, cooling load formula, heating load calculation, MEP HVAC formulas, air conditioning calculation
0 Comments
Please do not enter any spam links in the comment box.